CALL
1-918-241-8880
FOR MORE
INFORMATION
|
QuikWater
110 North Garfield
Suite 100
Sand Springs, OK 74063
Fax: 918-241-8880
Sales@QuikWater.com
|
|
You can determine the preliminary heater size to meet
your requirements by using the chart below. But first,
you will need the following information to use the chart:
- Determine your total
hourly water usage during peak demand.
EXAMPLE: 6000 gallons / 60 minutes = 100 GPM
- Determine the water
temperature rise required
EXAMPLE: inlet 60ºF, outlet need 160ºF = temp rise
of 100ºF
The chart suggests a model 5000 to meet these
specific
needs.
Model |
Tank (Gals.) |
GPM Flow at Indicated
Temperature Rise ºF |
| 20ºF¹ |
40ºF¹ |
60ºF |
80ºF |
100ºF |
120ºF¹ |
140ºF |
| 600 |
70 |
60¹ |
30¹ |
20 |
15 |
12 |
10 |
8 |
| 1000 |
100 |
100¹ |
50¹ |
33 |
25 |
20 |
16 |
14 |
| 1750 |
175 |
175¹ |
87¹ |
58 |
43 |
35 |
29 |
25 |
| 2500 |
200 |
250¹ |
125¹ |
83 |
62 |
50 |
41 |
35 |
| 3500 |
340 |
350¹ |
175¹ |
117 |
87 |
70 |
58 |
50 |
| 5000 |
425 |
500¹ |
250¹ |
167 |
125 |
100 |
83 |
71 |
| 6000 |
540 |
600¹ |
300¹ |
200 |
150 |
120 |
100 |
85 |
| 8000 |
775 |
800¹ |
400¹ |
267 |
200 |
160 |
133 |
114 |
| 10.0 |
1,050 |
1000¹ |
500¹ |
333 |
250 |
200 |
166 |
142 |
| 12.5 |
1,175 |
1250¹ |
625¹ |
417 |
312 |
250 |
208 |
178 |
| 15.0 |
1,400 |
1500¹ |
750¹ |
500 |
375 |
300 |
250 |
214 |
| 17.5 |
1,750 |
1750¹ |
875¹ |
583 |
437 |
350 |
291 |
250 |
| 20.0 |
1,900 |
2000¹ |
1000¹ |
667 |
500 |
400 |
333 |
285 |
| 25.0 |
2,350 |
2500¹ |
1250¹ |
833 |
625 |
500 |
416 |
357 |
| 30.0 |
2,750 |
3000¹ |
1500¹ |
1000 |
750 |
600 |
500 |
428 |
| 35.0 |
3,225 |
3500¹ |
1750¹ |
1167 |
875 |
700 |
583 |
500 |
|
|
Rated performance is based on 60ºF inlet water with 100ºF
temperature rise. For higher temperature rating,
consult factory.
Variations in the QW heater design
may be required to achieve all flow parameters. Please consult factory if required
temperature rise
(ºF out - ºFin) is less than 60ºF.
Standard ratings are based on 1000'
elevation. Burners are subject to 4% deration for each additional 1000'.
Tabulated flow rates represent 99%
efficient heater operation when inlet water temperature is 60ºF or below.
A.) Model x 1000 = BTU/hr capacity
through Model 8000.
B.) Models 10.0 through 35.0 x 1 million = BTU/hr capacity.
|
|
|